EKL15-63H RCBO | 6kA/10kA Breaking Capacity | Type A Protection
Inquire
| Mode | Electronic |
| Type | AC, A |
| Rated current (In) | 6, 10, 16, 20, 25, 32, 40A |
| Poles | 1P+N(Pole N could be On/Off) |
| Rated voltage (Ue) | 240V~ |
| Insulation voltage (Ui) | 400V |
| Rated frequency | 50Hz |
| Rated residual operating current(I△n) | 10, 30, 100, 300mA |
| Break time under | ≤0.1s |
| Rated breaking capacity | 6,000A |
| Energy limiting class | 3 |
| Rated impulse withstand voltage (1.2/50) Uimp | 4,000V |
| Dielectric test voltage at ind.Freq. for 1min | 2kV |
| Thermal release characteristic | (1.13-1.45) x In |
| Magnetic release characteristic | B:(3-5) x In, C:(5-10) x In |
| Electrical life | 4,000 Cycles |
| Mechanical life | 10,000 Cycles |
| Contact position indicator | Yes |
| Protection degree | IP20 |
| Ambient temperature | -25℃ to +40℃, Max.95% humidity |
| Terminal connection type | Cable/Pin-type busbar |
| Max. terminalsizeforcable | 16mm2 |
| Max. tightening torque | 2.5Nm 22In-lbs |
| Installation | Mounting on 35mm DIN rail |
| Connection | From top |