| Standard | IEC/EN60898-1 | IEC/EN60947-2 |
| Protection | Overcurrent and short circuit | |
| Type of trip | Thermo-magnetic | |
| No.of poles | 1P,1P+N,2P,3P,3P+N,4P | |
| Rated currents (In) | 1,2,3,4,5,6,10,16,20,25,32,40,50,63A | |
| Rated voltage (Ue) | 240/415V~ | |
| Rated frequency | 50/60Hz | |
| Rated breaking capacity | 6,000A | |
| Energy Limiting Class | 3 | |
| Rated impulse withstand voltage (1.2/50) Uimp | 6,000V | |
| Dielectric test voltage at Ind. Freq.for 1 min | 2kV | |
| Thermal release characteristic | (1.13-1.45) x In | (1.05-1.30) x In |
| Magnetic release characteristic | B:(3-5) x In, C:(5-10) x In | (8-12) x In |
| Electrical life | 8,000 Cycles | |
| Mechanical life | 20,000 Cycles | |
| Contact position indicator | Yes | |
| Protection degree | IP20 | |
| Ambient temperature | -5℃ to +40℃, Max.95% humidity | |
| Terminal connection type | Cable/Pin-type busbar | |
| Max. terminal size for cable | 25mm2 | |
| Max. tightening torque | 2.5N.m | |
| Installation | Mounting on 35mm DIN rail | |
| Connection | From top and bottom | |