EKL6-100(H) 6kA 10kA RCCB Circuit Breaker

EKL6-100(H) 6kA 10kA RCCB Circuit Breaker

Inquire NOW PDF
EKL6-100(H) 6kA 10kA RCCB Circuit Breaker
EKL6-100(H) 6kA 10kA RCCB Circuit Breaker

EKL6-100(H) 6kA 10kA RCCB Circuit Breaker

Inquire NOW PDF

Technical Data

Standard IEC/EN61008-1
Protection Ground fault
Type of trip Electro-magnetic
Type of protection (electric leakage) AC,A,G,S
No.of poles 2P(1P+N), 4P(3P+N) , N Pole on left
Rated currents (In) 16,25,32,40,63,80,100A
Rated sensitivity currents I△n 10,30,100,300mA (10mA only for In=16-25A)
Residual current off-time under I△n ≤ 0.1s
Rated residual making and breaking capacity(I△m) 500A(In≤50A), 10In(In>50A)
Rated voltage (Ue) 1P+N: 230/240V~, 3P+N:400/415V~
Rated frequency 50/60Hz
Rated breaking capacity 6,000A, 10,000A
SCPD fuse
Dielectric test voltage at Ind. Freq.f 4,000V
Rated impulse withstand voltage (1.2/50) Uimp 2kV
or 1 min 2,000 Cycles
Electrical life 4,000 Cycles
Mechanical life Yes
Contact position indicator Yes
Ground fault indicator IP20
Protection degree Cable/Pin-type busbar/Fork-type busb
Ambient temperature -25℃ to +40℃, Max.95% humidity
Terminal connection type ar
Max. terminal size for cable 35mm²
Max. tightening torque 2.5N.m
Installation Mounting on 35mm DIN rail
Connection From top and bottom

Dimensions

 

Circuit Diagram

Recommend Products

Inquiry Basket()
Send An Inquiry

Get in Touch

×
We value your privacy
We use cookies to provide you with a better online experience, analyse and measure website usage, and assist in our marketing efforts.
Accept All