EKDC2 60-240kW DC Fast Charger | High Power EV Charging Station
EKDC2 60–240 kW DC fast EV charging station with dual-gun output, CCS1/CCS2/GB/T/CHAdeMO connector options and OCPP 1.6J support for commercial, fleet and EPC projects.
● Product type: Floor-standing DC fast EV charging station
● Series / variant: EKDC2, 60–240 kW
● Power options: 60, 80, 120, 150, 160, 180, 240 kW
● Charging layout: Dual gun
● Connector options: CCS1, CCS2, GB/T, CHAdeMO
● Input voltage: AC 380–415V, 3P+N+PE, 50/60Hz
● Output voltage: 50–1000V DC
● Charging access: Plug & charge, RFID, APP
● Network and protocol: OCPP 1.6J, Ethernet, optional 4G and Wi-Fi
● Installation: Floor mounting
● Protection: Overcurrent, short-circuit, ground, surge, voltage, frequency and temperature protection; emergency stop
● Environmental protection: IP54, IK10 cabinet protection
Product Profile
Product Profile
EKDC2 is a floor-standing DC fast EV charging station for commercial charging sites, fleet depots, public parking and EPC projects. The series covers 60–240 kW and uses a dual-gun configuration. Select the power rating, connector mix and connectivity options according to the local vehicle standard, available grid capacity and charging-management requirements.
EKDC2 supports CCS1, CCS2, GB/T or CHAdeMO connector options and OCPP 1.6J communication. Ethernet is available, with 4G and Wi-Fi available as options. Charging sessions can be started through plug & charge, RFID or APP workflows. The station supports remote upgrades, remote diagnostics and real-time charging-status monitoring.
|
Commercial Configuration
|
Operation and Connectivity
|
|
Protection Functions
|
Project Information for Selection
|
For smaller 20–60 kW sites, see the EKDC1 series. For higher-power projects above the EKDC2 range, see the EKDC3 and EKDC6 DC fast charging solutions.
Model Preparation Meaning
Model Preparation Meaning
Example type code structure: EK DC2 - CC 120 B
- EK — ETEK company code
- DC2 — DC EV charging station design number
- CC — Connector configuration
- 120 — Total rated power in kW
- B — Power module code
| Code section | Available meaning |
|---|---|
| Connector configuration | CC: 2 × CCS2; AA: 2 × CCS1; GG: 2 × GB/T; JJ: 2 × CHAdeMO |
| Mixed connector configuration | CG: CCS2 + GB/T; CA: CCS2 + CCS1; CJ: CCS2 + CHAdeMO; GA: GB/T + CCS1; GJ: GB/T + CHAdeMO; AJ: CCS1 + CHAdeMO |
| Power code | 60, 80, 120, 150, 160, 180, 240 kW |
| Power module code | A, B, C |
Technical Data
Technical Data
| Item | EKDC2 60–240 kW |
|---|---|
| Product type | Floor-standing DC fast EV charging station |
| Power | 60 / 80 / 120 / 150 / 160 / 180 / 240 kW |
| Connector | GB/T / CCS1 / CHAdeMO / CCS2 optional |
| Connector number | Dual gun |
| Input voltage | AC 380–415V, 3P+N+PE |
| Frequency | 50/60Hz |
| Output voltage | 50–1000V DC |
| Status indicator | Green / Yellow / Red |
| User interface | 7.0-inch LCD display |
| RFID | Mifare ISO/IEC 14443 A |
| Emergency stop button | Yes |
| Charging modes | Plug & charge, RFID, APP |
| Communication protocol | OCPP 1.6J or other |
| Communication | Ethernet / 4G / Wi-Fi; 4G and Wi-Fi optional |
| Electrical protection | Overcurrent, short circuit, ground, surge, over/under voltage, over/under frequency and over/under temperature protection |
| Energy meter | Yes |
| Charging standards | EN/IEC 61851-1:2019; IEC 61851-1:2017; EN 61851-23:2014; IEC 61851-23:2014; EN 61851-24:2014; IEC 61851-24:2014; EN/IEC 61000-6-2:2019; EN/IEC 61000-6-4:2019; EN/IEC 61851-21-2:2021 |
| Ingress protection | IP54 |
| Impact protection | IK10; screen IK08 |
| Working temperature | -30°C to +50°C |
| Working humidity | 5%–95% |
| Working altitude | < 2000m |
| Product dimensions | With swing arm: H 2000 × L 850 × W 600 mm; without swing arm: H 1800 × L 850 × W 600 mm |
| Installation mode | Floor mounting |
| Certificate | TUV, SUD, CB, CE, UKCA |