EKEPC2-C/S RS485 Communication Setup Guide

Publish Time: Author: ETEK ELECTRIC Views: 102
Quick answer: To set RS485 communication for an EKEPC2-C/S EPC controller, confirm the RS485 A/B wiring, set the correct baud rate and communication address, match the Modbus or controller parameters on the host device, then test data reading before commissioning the EV charging controller system.

How to setting RS485 communication for EKEPC2-C/S EPC controller
This article introduces the RS485 communication for the ETEC brand EKEPC2-C and EKEPC2-S model charging pile EPC Controller.

1.Communication Interface Wiring

Connected the A, B terminal to a USB-RS485 converter’s A+,B-,no need connect GND,then you can find the equipement COM

 

2.Protocol,boad rate and register address

EKEPC2-C 和EKEPC2-S  Support modbus communication protocol, baud rate: 9600, 8, n, 1 Address: 1-255 Default: 255 (broadcast address)

寄存器地址

Register address

数据说明(掉电保护)

Data description (power failure protection)

(R/W)

数据类型

type of data

默认值

Defaults

86

过压保护值(0.01V)

Overvoltage protection value (0.01V)

R/W

16位整型

16-bit integer

26500

87

欠压保护(0.01V)

Under-voltage protection (0.01V)

R/W

16位整型

16-bit integer

16500

88

过电流保护值(XX%)

Overcurrent protection value (XX%)

R/W

16位整型

16-bit integer

120

89

远程启动停止(0无效、1启动、2停止)

Remote start and stop (0 invalid, 1 start, 2 stop)

R/W

16位整型

16-bit integer

0

90

1#电表A相电压地址号(65535为无效地址)

1# Meter A-phase voltage address number (65535 is an invalid address)

R/W

16位整型

16-bit integer

65535

91

1#电表B相电压地址号(65535为无效地址)

1# Meter B-phase voltage address number (65535 is an invalid address)

R/W

16位整型

16-bit integer

65535

92

1#电表C相电压地址号(65535为无效地址)

1# Meter C-phase voltage address number (65535 is an invalid address)

R/W

16位整型

16-bit integer

65535

93

1#总电流地址号(65535为无效地址)

1# total current address number (65535 is an invalid address)

R/W

16位整型

16-bit integer

65535

94

1#总功率地址号(65535为无效地址)

1# total power address number (65535 is an invalid address)

R/W

16位整型

16-bit integer

65535

95

1#总电量地址号(65535为无效地址)

1# Total KWH address number (65535 is an invalid address)

R/W

16位整型

16-bit integer

65535

96

2#电表的DLB电流地址(65535为无效地址)

2# DLB current address of the meter (65535 is an invalid address)

R/W

16位整型

16-bit integer

65535

97-99

备用

spare

R/W

16位整型

16-bit integer

0

100

设备地址号

Device address number

R/W

16位整型

16-bit integer

255

101

DLB 最大启动电流(0.01A)

DLB maximum startup current (0.01A)

R/W

16位整型

16-bit integer

3500

102

DLB 最大保护电流(0.01A)

DLB maximum protection current (0.01A)

R/W

16位整型

16-bit integer

4500

103

DLB电流互感器的最大电流(0.01A) 

Maximum current of DLB current transformer (0.01A)

R/W

16位整型

16-bit integer

10000

104

DLB电流采校准系数

DLB current sampling calibration coefficient

R/W

16位整型

16-bit integer

1270

105-108

备用

spare

R/W

 

 

109

Max Output Current  PWM Duty cycle(*100)

 

R/W

16位整型

16-bit integer

9000

110

RCMU功能选择    0禁用 1启用,其他值时由DIP开关选择

RCMU function selection 0 disable 1 enable, other values are selected by DIP switch

R/W

16位整型

16-bit integer

3

111

 RFID功能选择    0禁用 1启用,其他值时由DIP开关选择

RFID function selection 0 disable 1 enable, other values are selected by DIP switch

R/W

16位整型

16-bit integer

3

112

锁功能选择   0禁用 1启用,其他值时由DIP开关选择

Lock function selection 0 disable 1 enable, other values are selected by DIP switch

R/W

16位整型

16-bit integer

3

113

线缆功能版选择 0禁用 1启用,其他值时由DIP开关选择

Cable function version selection 0 disable 1 enable, other values are selected by DIP switch

R/W

16位整型

16-bit integer

3

114

DLB功能选择 0禁用 1启用,其他值时由DIP开关选择

DLB function selection 0 disable 1 enable, other values are selected by DIP switch

R/W

16位整型

16-bit integer

3

115

DLB的PID控制参数P

PID control parameter P of DLB

R/W

16位整型

16-bit integer

100

116

DLB的PID控制参数I

PID control parameter I of DLB

R/W

16位整型

16-bit integer

1

117

DLB的PID控制参数D

PID control parameter D of DLB

R/W

16位整型

16-bit integer

100

118-119

控制器ID号 最多9位数

Controller ID number Up to 9 digits

R/W

32位

32 bit

0

120

温度修正(差多少输入多少)H

Temperature correction (how much difference is input) H

R/W

16位整型

16-bit integer

1024

121

温度修正(差多少输入多少)L

Temperature correction (how much difference is input) L

R/W

16位整型

16-bit integer

0

122

解除温度保护值

Release temperature protection value

R/W

16位整型

16-bit integer

600

123

最高温度保护值

Maximum temperature protection value

R/W

16位整型

16-bit integer

700

124

频率修正(差多少输入多少)

Frequency correction (how much difference is input)

R/W

16位整型

16-bit integer

65528

125

占空比修正(差多少输入多少)

Duty cycle correction (how much difference is input)

R/W

16位整型

16-bit integer

0

126

商标选择0无1WATT 2VOLU

Trademark selection 0 none 1WATT 2VOLU

R/W

16位整型

16-bit integer

0

127

极数选择:1P  3P  默认为:1

Pole selection: 1P 3P Default: 1

R/W

16位整型

16-bit integer

1

128

第一档电流设定值PWM

The first gear current setting value PWM

R/W

16位整型

16-bit integer

1667

129

第二档电流设定值PWM

The second gear current setting value PWM

R/W

16位整型

16-bit integer

2167

130

第三档电流设定值PWM

The third gear current setting value PWM

R/W

16位整型

16-bit integer

3333

131

第四档电流设定值PWM

The Fourth gear current setting value PWM

R/W

16位整型

16-bit integer

4167

132

第五档电流设定值PWM

The Fifth gear current setting value PWM

R/W

16位整型

16-bit integer

5333

133

第六档电流设定值PWM

The sixth gear current setting value PWM

R/W

16位整型

16-bit integer

5333

134-139

备用

spare

R/W

 

 

140

软件版本号 

Software version number

R

16位整型

16-bit integer

1002

141

当前工作状态 :   对应状态0-11

Current working status: Corresponding status 0-11

R

16位整型

16-bit integer

 

142

线缆规格的PWM值

PWM value for cable gauge

R

16位整型

16-bit integer

 

143

RCMU状态 00没有选择01 工作正常 02 自检失败 03 充电电路有漏电

RCMU status 00 is not selected 01 works normally 02 self-test failed 03 charging circuit has leakage

R

16位整型

16-bit integer

 

144

RFID状态 00没选择 01 IC卡没有操作 02 IC卡关闭 03 IC卡打开

RFID status 00 Not selected 01 IC card not operating 02 IC card closed 03 IC card open

R

16位整型

16-bit integer

 

145

锁状态    00没有选择01 上锁 02解锁 03故障

RFID status 00 Not selected 01 IC card not operating 02 IC card closed 03 IC card open

R

16位整型

16-bit integer

 

146

 DLB功能的当前电流值

Current value of the DLB function

R

16位整型

16-bit integer

 

147

充电桩当前电流值   0-200.0A

Current value of charging pile 0-200.0A

R

16位整型

16-bit integer

暂时无效

temporarily invalid

148

充电桩当前电压值)  0-500.0V

Current voltage value of charging pile) 0-500.0V

R

16位整型

16-bit integer

暂时无效

temporarily invalid

149

充电桩当前功率值  0-22000W

Current power value of charging pile 0-22000W

R

16位整型

16-bit integer

暂时无效

temporarily invalid

150

参考电流的校准值AD值

Calibration value AD value of reference current

R

16位整型

16-bit integer

暂时无效

temporarily invalid

151

旋转开关设置的电流对应的PWM占空比  

PWM duty cycle corresponding to the current set by the rotary switch

R

16位整型

16-bit integer

 

152

当前输出PWM占空比

Current output PWM duty cycle

R

16位整型

16-bit integer

 

153

CP正电压

CP positive voltage

R

16位整型

16-bit integer

暂时无效

temporarily invalid

154

CP负电压

CP negative voltage

R

16位整型

16-bit integer

暂时无效

temporarily invalid

155

超电流计数

Overcurrent count

R

16位整型

16-bit integer

暂时无效

temporarily invalid

156

小电流计数

Small current count

R

16位整型

16-bit integer

暂时无效

temporarily invalid

157

当前温度

Current Temperature

R

16位整型

16-bit integer

 

158

温度AD

temperature AD

R

16位整型

16-bit integer

暂时无效

temporarily invalid

159

1#电表A相电压

1# meter A phase voltage

R

16位整型

16-bit integer

 

160

1#电表B相电压

1# meter B phase voltage

R

16位整型

16-bit integer

 

161

1#电表C相电压

1# meter C phase voltage

R

16位整型

16-bit integer

 

162

1#电表电流

1# meter current

R

16位整型

16-bit integer

 

163

1#电表总功率

1# total power of the meter

R

16位整型

16-bit integer

 

164-165

1#电表总电量

1# The total electricity of the meter

R

32位整型

32-bit integer

 

166

2#DLB电表上的电流

2# The current on the DLB meter

R

16位整型

16-bit integer

 

3.Electric meter connection parameter settings

Register address: 90-95 register value is: a) =65535, this time the address is invalid, all data will be in accordance with the controller set value to display and judge. b) = When the external communication address is 1, the controller will read the corresponding value in the meter. See Table 1/2 below

If the DLB function is enabled and register 96 data is a) =65535, the controller will read the sampling value of the external current transformer. b) = Register number of current value in the ammeter with external communication address 2, the controller will read the current value in the ammeter. See Table 1/2 below

Table 1:

1.EKEM2D or EKEM4D charger power metering meter, communication protocol Modbus-RTU 9600, n,8,1; address number: 01H

 

Name

Addr(Dec)

Length

Property

Type

Controller address

L 1 phase voltage

2304

4

Float

R

90

L 2 phase voltage

2306/65535

4

Float

R

91

L 3 phase voltage

2308/65535

4

Float

R

92

L 1 phase current

2310

4

Float

R

 

L 2 phase current

2312/65535

4

Float

R

 

L 3 phase current

2314/65535

4

Float

R

 

Average current

2318/6

4

Float

R

93

Sum of three-phase current

2320

4

Float

R

 

Total active power

2322

4

Float

R

94

L1-2 line voltage

2324

4

Float

R

 

L1-2 line voltage

2326

4

Float

R

 

L1-2 line voltage

2328

4

Float

R

 

Three-phase line voltage average

2330

4

Float

R

 

There is always power

2332

4

Float

R

95

  2.EKEM2D or EKEM4D DLB current monitory meter, communication protocol Modbus-RTU 9600, n,8,1; address number: 02H

Name

Addr(Dec)

Length

Property

Type

Controller address

Average current

2318

4

Float

R

96

Maximum current

2334

4

Float

R

96

Table 2:

   1) SDM120M/SDM73 charger power metering meter , communication protocol Modbus-RTU 9600, n,8,1; address number: 01H

 

Name

Addr(Dec)

Length

Property

Type

Controller address

L 1 phase voltage

0

4

Float

R

90

L 2 phase voltage

2

4

Float

R

91

L 3 phase voltage

4

4

Float

R

92

L 1 phase current

6

4

Float

R

 

L 2 phase current

8

4

Float

R

 

L 3 phase current

10

4

Float

R

 

 Average voltage

42

4

Float

R

 

Average current

46

4

Float

R

93

Sum of three-phase current

48

4

Float

R

 

Total active power

52

4

Float

R

94

L1-2 line voltage

200

4

Float

R

 

L1-2 line voltage

202

4

Float

R

 

L1-2 line voltage

204

4

Float

R

 

Three-phase line voltage average

2.6

4

Float

R

 

There is always power

342

4

Float

R

95

   2) SDM120M/SDM73 DLB current monitory meter, communication protocol Modbus-RTU 9600, n,8,1; Address number: 02H

Name

Addr(Dec)

Length

Property

Type

Controller address

Average current

46/6

4

Float

R

96

Max. current

396

4

Float

R

96